Skip to main content

Recycled Water Quality Data

Recycled water produced by Delta Diablo meets all regulatory requirements for unrestricted non-potable reuse. 
The Delta Diablo laboratory tests the parameters listed in the table on a monthly or quarterly basis to ensure recycled water meets the needs of our industrial and landscape irrigation customers.
Recycled Water Quality Data, Calendar Year 2020

Constituent Unit Average Range
pH standard unit 7.4 7.2 - 7.6
Alkalinity (as CaCO3) mg/L 238 220 - 250
Total Hardness (as CaCO3) mg/L 185 150 - 200
Calcium mg/L 38 31 - 46
Magnesium mg/L 23 18 - 24
Manganese ug/L 53 42 - 64
Potassium mg/L 17 16 - 19
Sodium mg/L 163 140 - 190
Conductivity µmhos/cm 1516 1414 - 1664
Total Dissolved Solids mg/L 724 670 - 790
Chloride mg/L 198 120 - 289
Sulfate mg/L 196 170 - 240
Silica (as SiO2) mg/L 17 15 - 20
Total Nitrogen mg/L 48 42 - 53
Total Kjeldahl Nitrogen mg/L 47 41 - 52
Ammonia mg/L 41 36 - 47
Nitrate (as N) mg/L 2.07 0.83 - 7.10
Nitrite (as N) mg/L 1.63 0.03 - 6.70
Phosphate mg/L 0.18 0.03 - 0.88
Total Coliform Bacteria MPN 1.4 <1 - 37.3
Turbidity NTU 0.71 0.26 - 1.28

Abbreviations:

mg/L = milligrams per liter

µmhos = microhms per centimeter

µg/L = micrograms per liter

MPN = most probable number

NTU = Nephelometric Turbidity Units